Time characteristic curve based earth fault relay selectivity assessment for optimal overcurrent relay coordination in distribution networks

Yükleniyor...
Küçük Resim

Tarih

2022

Dergi Başlığı

Dergi ISSN

Cilt Başlığı

Yayıncı

IEEE

Erişim Hakkı

info:eu-repo/semantics/embargoedAccess

Özet

Coordination of overcurrent relays has been handled with optimization techniques. Time and pick up settings are optimized by using three-phase fault magnitudes. Generally, Standard Inverse Characteristic (SIC) has been used for threephase fault protection settings. However, single line to earth fault is the most common fault types in distribution networks. Definite Time Characteristic (DTC) is, widely, used for coordination of earth fault relays. Topology type, neutral earthing resistance and capacitive currents of underground cables may cause selectivity issues when DTC is used for the coordination. In this work, time characteristic curve (TCC) based earth fault relay selectivity assessment carried out on distribution network. Different earthing resistance and TCC are taken into account during optimization processes. Results show that both DTC and SIC have issues in terms of operating time and selective protection.

Açıklama

Anahtar Kelimeler

optimization, relay coordination, earth fault

Kaynak

2022 57th International Universities Power Engineering Conference: Big Data and Smart Grids, UPEC 2022 - Proceedings